Regulatory Information

Please select your state below to learn more about your state’s regulatory information.

Alabama

Code Requirements for Nail Salons in ALABAMA

What the IMC Code Requires

For new nail salons in the state of Alabama, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station.  Each system must:

  • Exhaust a minimum of 50 CFM (cubic feet per minute) per station
  • Have exhaust inlets no more than 12 inches from the point of chemical application

This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.

Why Proper Ventilation Matters

Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.

Exhaust Flow and Placement

IMC Section 403.3 defines how source capture ventilation must operate:

  • Exhaust rate: at least 50 CFM per station
  • Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
  • Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)

When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.

Code-Compliant Solution

The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.

 

Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.

Alaska

Code Requirements for Nail Salons in ALASKA

What the IMC Code Requires

For new nail salons in the state of Alaska, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station.  Each system must:

  • Exhaust a minimum of 50 CFM (cubic feet per minute) per station
  • Have exhaust inlets no more than 12 inches from the point of chemical application

This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.

Why Proper Ventilation Matters

Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.

Exhaust Flow and Placement

IMC Section 403.3 defines how source capture ventilation must operate:

  • Exhaust rate: at least 50 CFM per station
  • Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
  • Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)

When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.

Code-Compliant Solution

The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.

 

Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.

Arizona

IMC Code Requirements for Nail Salons in ARIZONA

What the IMC Code Requires

For new nail salons in the state of Arizona, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station.  Each system must:

  • Exhaust a minimum of 50 CFM (cubic feet per minute) per station
  • Have exhaust inlets no more than 12 inches from the point of chemical application

This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.

Why Proper Ventilation Matters

Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.

Exhaust Flow and Placement

IMC Section 403.3 defines how source capture ventilation must operate:

  • Exhaust rate: at least 50 CFM per station
  • Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
  • Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)

When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.

Code-Compliant Solution

The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.

 

Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.

Arkansas

Code Requirements for Nail Salons in ARKANSAS

What the IMC Code Requires

For new nail salons in the state of Arkansas, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station.  Each system must:

  • Exhaust a minimum of 50 CFM (cubic feet per minute) per station
  • Have exhaust inlets no more than 12 inches from the point of chemical application

This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.

Why Proper Ventilation Matters

Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.

Exhaust Flow and Placement

IMC Section 403.3 defines how source capture ventilation must operate:

  • Exhaust rate: at least 50 CFM per station
  • Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
  • Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)

When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.

Code-Compliant Solution

The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.

 

Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.

Colorado

IMC Code Requirements for Nail Salons in COLORADO

What the IMC Code Requires

For new nail salons in the state of Colorado, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:

  • Exhaust a minimum of 50 CFM (cubic feet per minute) per station
  • Have exhaust inlets no more than 12 inches from the point of chemical application

This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.

Why Proper Ventilation Matters

Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.

Exhaust Flow and Placement

IMC Section 403.3 defines how source capture ventilation must operate:

  • Exhaust rate: at least 50 CFM per station
  • Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
  • Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)

When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.

Code-Compliant Solution

The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.

 

Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.

Connecticut

IMC Code Requirements for Nail Salons in CONNECTICUT

What the IMC Code Requires

For new nail salons in the state of Connecticut, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:

  • Exhaust a minimum of 50 CFM (cubic feet per minute) per station
  • Have exhaust inlets no more than 12 inches from the point of chemical application

This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.

Why Proper Ventilation Matters

Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.

Exhaust Flow and Placement

IMC Section 403.3 defines how source capture ventilation must operate:

  • Exhaust rate: at least 50 CFM per station
  • Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
  • Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)

When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.

Code-Compliant Solution

The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.

 

Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.

Florida

IMC Code Requirements for Nail Salons in FLORIDA

What the IMC Code Requires

For new nail salons in the state of Florida, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station.
Each system must:

  • Exhaust a minimum of 50 CFM (cubic feet per minute) per station
  • Have exhaust inlets no more than 12 inches from the point of chemical application

This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.

Why Proper Ventilation Matters

Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.

Exhaust Flow and Placement

IMC Section 403.3 defines how source capture ventilation must operate:

  • Exhaust rate: at least 50 CFM per station
  • Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
  • Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)

When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.

Code-Compliant Solution

The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.

 

Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.

Georgia

IMC Code Requirements for Nail Salons in GEORGIA

What the IMC Code Requires

For new nail salons in the state of Georgia, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:

  • Exhaust a minimum of 50 CFM (cubic feet per minute) per station
  • Have exhaust inlets no more than 12 inches from the point of chemical application

This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.

Why Proper Ventilation Matters

Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.

Exhaust Flow and Placement

IMC Section 403.3 defines how source capture ventilation must operate:

  • Exhaust rate: at least 50 CFM per station
  • Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
  • Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)

When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.

Code-Compliant Solution

The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.

 

Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.

Illinois

IMC Code Requirements for Nail Salons in ILLINOIS

What the IMC Code Requires

For new nail salons in the state of Illinois, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station.
Each system must:

  • Exhaust a minimum of 50 CFM (cubic feet per minute) per station
  • Have exhaust inlets no more than 12 inches from the point of chemical application

This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.

Why Proper Ventilation Matters

Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.

Exhaust Flow and Placement

IMC Section 403.3 defines how source capture ventilation must operate:

  • Exhaust rate: at least 50 CFM per station
  • Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
  • Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)

When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.

Code-Compliant Solution

The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.

 

Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.

Indiana

IMC Code Requirements for Nail Salons in INDIANA

What the IMC Code Requires

For new nail salons in the state of Indiana, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:

  • Exhaust a minimum of 50 CFM (cubic feet per minute) per station
  • Have exhaust inlets no more than 12 inches from the point of chemical application

This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.

Why Proper Ventilation Matters

Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.

Exhaust Flow and Placement

IMC Section 403.3 defines how source capture ventilation must operate:

  • Exhaust rate: at least 50 CFM per station
  • Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
  • Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)

When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.

Code-Compliant Solution

The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.

 

Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.

Iowa

Code Requirements for Nail Salons in IOWA

What the IMC Code Requires

For new nail salons in the state of Iowa, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station.  Each system must:

  • Exhaust a minimum of 50 CFM (cubic feet per minute) per station
  • Have exhaust inlets no more than 12 inches from the point of chemical application

This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.

Why Proper Ventilation Matters

Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.

Exhaust Flow and Placement

IMC Section 403.3 defines how source capture ventilation must operate:

  • Exhaust rate: at least 50 CFM per station
  • Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
  • Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)

When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.

Code-Compliant Solution

The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.

 

Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.

Louisiana

IMC Code Requirements for Nail Salons in LOUISIANA

What the IMC Code Requires

For new nail salons in the state of Louisiana, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:

  • Exhaust a minimum of 50 CFM (cubic feet per minute) per station
  • Have exhaust inlets no more than 12 inches from the point of chemical application

This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.

Why Proper Ventilation Matters

Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.

Exhaust Flow and Placement

IMC Section 403.3 defines how source capture ventilation must operate:

  • Exhaust rate: at least 50 CFM per station
  • Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
  • Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)

When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.

Code-Compliant Solution

The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.

 

Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.

Maine

Code Requirements for Nail Salons in MAINE

What the IMC Code Requires

For new nail salons in the state of Maine, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station.  Each system must:

  • Exhaust a minimum of 50 CFM (cubic feet per minute) per station
  • Have exhaust inlets no more than 12 inches from the point of chemical application

This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.

Why Proper Ventilation Matters

Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.

Exhaust Flow and Placement

IMC Section 403.3 defines how source capture ventilation must operate:

  • Exhaust rate: at least 50 CFM per station
  • Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
  • Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)

When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.

Code-Compliant Solution

The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.

 

Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.

Maryland

IMC Code Requirements for Nail Salons in MARYLAND

What the IMC Code Requires

For new nail salons in the state of Maryland, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:

  • Exhaust a minimum of 50 CFM (cubic feet per minute) per station
  • Have exhaust inlets no more than 12 inches from the point of chemical application

This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.

Why Proper Ventilation Matters

Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.

Exhaust Flow and Placement

IMC Section 403.3 defines how source capture ventilation must operate:

  • Exhaust rate: at least 50 CFM per station
  • Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
  • Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)

When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.

Code-Compliant Solution

The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.

 

Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.

Massachusetts

IMC Code Requirements for Nail Salons in MASSACHUSETTS

What the IMC Code Requires

For new nail salons in the state of Massachusetts, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:

  • Exhaust a minimum of 50 CFM (cubic feet per minute) per station
  • Have exhaust inlets no more than 12 inches from the point of chemical application

This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.

Why Proper Ventilation Matters

Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.

Exhaust Flow and Placement

IMC Section 403.3 defines how source capture ventilation must operate:

  • Exhaust rate: at least 50 CFM per station
  • Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
  • Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)

When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.

Code-Compliant Solution

The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.

 

Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.

Michigan

IMC Code Requirements for Nail Salons in MICHIGAN

What the IMC Code Requires

For new nail salons in the state of Michigan, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:

  • Exhaust a minimum of 50 CFM (cubic feet per minute) per station
  • Have exhaust inlets no more than 12 inches from the point of chemical application

This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.

Why Proper Ventilation Matters

Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.

Exhaust Flow and Placement

IMC Section 403.3 defines how source capture ventilation must operate:

  • Exhaust rate: at least 50 CFM per station
  • Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
  • Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)

When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.

Code-Compliant Solution

The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.

 

Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.

Minnesota

IMC Code Requirements for Nail Salons in MINNESOTA

What the IMC Code Requires

For new nail salons in the state of Minnesota, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:

  • Exhaust a minimum of 50 CFM (cubic feet per minute) per station
  • Have exhaust inlets no more than 12 inches from the point of chemical application

This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.

Why Proper Ventilation Matters

Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.

Exhaust Flow and Placement

IMC Section 403.3 defines how source capture ventilation must operate:

  • Exhaust rate: at least 50 CFM per station
  • Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
  • Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)

When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.

Code-Compliant Solution

The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.

 

Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.

Missouri

IMC Code Requirements for Nail Salons in MISSOURI

What the IMC Code Requires

For new nail salons in the state of Missouri, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:

  • Exhaust a minimum of 50 CFM (cubic feet per minute) per station
  • Have exhaust inlets no more than 12 inches from the point of chemical application

This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.

Why Proper Ventilation Matters

Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.

Exhaust Flow and Placement

IMC Section 403.3 defines how source capture ventilation must operate:

  • Exhaust rate: at least 50 CFM per station
  • Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
  • Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)

When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.

Code-Compliant Solution

The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.

 

Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.

Montana

Code Requirements for Nail Salons in MONTANA

What the IMC Code Requires

For new nail salons in the state of Montana, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station.  Each system must:

  • Exhaust a minimum of 50 CFM (cubic feet per minute) per station
  • Have exhaust inlets no more than 12 inches from the point of chemical application

This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.

Why Proper Ventilation Matters

Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.

Exhaust Flow and Placement

IMC Section 403.3 defines how source capture ventilation must operate:

  • Exhaust rate: at least 50 CFM per station
  • Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
  • Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)

When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.

Code-Compliant Solution

The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.

 

Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.

Nevada

IMC Code Requirements for Nail Salons in NEVADA

What the IMC Code Requires

For new nail salons in the state of Nevada, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:

  • Exhaust a minimum of 50 CFM (cubic feet per minute) per station
  • Have exhaust inlets no more than 12 inches from the point of chemical application

This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.

Why Proper Ventilation Matters

Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.

Exhaust Flow and Placement

IMC Section 403.3 defines how source capture ventilation must operate:

  • Exhaust rate: at least 50 CFM per station
  • Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
  • Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)

When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.

Code-Compliant Solution

The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.

 

Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.

New Hampshire

Code Requirements for Nail Salons in NEW HAMPSHIRE

What the IMC Code Requires

For new nail salons in the state of New Hampshire, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station.  Each system must:

  • Exhaust a minimum of 50 CFM (cubic feet per minute) per station
  • Have exhaust inlets no more than 12 inches from the point of chemical application

This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.

Why Proper Ventilation Matters

Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.

Exhaust Flow and Placement

IMC Section 403.3 defines how source capture ventilation must operate:

  • Exhaust rate: at least 50 CFM per station
  • Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
  • Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)

When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.

Code-Compliant Solution

The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.

 

Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.

New Jersey

IMC Code Requirements for Nail Salons in NEW JERSEY

What the IMC Code Requires

For new nail salons in the state of New Jersey, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:

  • Exhaust a minimum of 50 CFM (cubic feet per minute) per station
  • Have exhaust inlets no more than 12 inches from the point of chemical application

This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.

Why Proper Ventilation Matters

Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.

Exhaust Flow and Placement

IMC Section 403.3 defines how source capture ventilation must operate:

  • Exhaust rate: at least 50 CFM per station
  • Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
  • Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)

When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.

Code-Compliant Solution

The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.

 

Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.

New York

IMC Code Requirements for Nail Salons in NEW YORK

What the IMC Code Requires

For new nail salons in the state of New York, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:

  • Exhaust a minimum of 50 CFM (cubic feet per minute) per station
  • Have exhaust inlets no more than 12 inches from the point of chemical application

This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.

Why Proper Ventilation Matters

Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.

Exhaust Flow and Placement

IMC Section 403.3 defines how source capture ventilation must operate:

  • Exhaust rate: at least 50 CFM per station
  • Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
  • Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)

When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.

Code-Compliant Solution

The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.

 

Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.

North Carolina

IMC Code Requirements for Nail Salons in NORTH CAROLINA

What the IMC Code Requires

For new nail salons in the state of North Carolina, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:

  • Exhaust a minimum of 50 CFM (cubic feet per minute) per station
  • Have exhaust inlets no more than 12 inches from the point of chemical application

This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.

Why Proper Ventilation Matters

Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.

Exhaust Flow and Placement

IMC Section 403.3 defines how source capture ventilation must operate:

  • Exhaust rate: at least 50 CFM per station
  • Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
  • Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)

When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.

Code-Compliant Solution

The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.

 

Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.

North Dakota

Code Requirements for Nail Salons in NORTH DAKOTA

What the IMC Code Requires

For new nail salons in the state of North Dakota, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station.  Each system must:

  • Exhaust a minimum of 50 CFM (cubic feet per minute) per station
  • Have exhaust inlets no more than 12 inches from the point of chemical application

This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.

Why Proper Ventilation Matters

Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.

Exhaust Flow and Placement

IMC Section 403.3 defines how source capture ventilation must operate:

  • Exhaust rate: at least 50 CFM per station
  • Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
  • Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)

When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.

Code-Compliant Solution

The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.

 

Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.

Ohio

IMC Code Requirements for Nail Salons in OHIO

What the IMC Code Requires

For new nail salons in the state of Ohio, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station.
Each system must:

  • Exhaust a minimum of 50 CFM (cubic feet per minute) per station
  • Have exhaust inlets no more than 12 inches from the point of chemical application

This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.

Why Proper Ventilation Matters

Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.

Exhaust Flow and Placement

IMC Section 403.3 defines how source capture ventilation must operate:

  • Exhaust rate: at least 50 CFM per station
  • Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
  • Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)

When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.

Code-Compliant Solution

The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.

 

Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.

Oregon

IMC Code Requirements for Nail Salons in OREGON

What the IMC Code Requires

For new nail salons in the state of Oregon, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:

  • Exhaust a minimum of 50 CFM (cubic feet per minute) per station
  • Have exhaust inlets no more than 12 inches from the point of chemical application

This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.

Why Proper Ventilation Matters

Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.

Exhaust Flow and Placement

IMC Section 403.3 defines how source capture ventilation must operate:

  • Exhaust rate: at least 50 CFM per station
  • Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
  • Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)

When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.

Code-Compliant Solution

The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.

 

Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.

Pennsylvania

IMC Code Requirements for Nail Salons in PENNSYLVANIA

What the IMC Code Requires

For new nail salons in the state of Pennsylvania, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:

  • Exhaust a minimum of 50 CFM (cubic feet per minute) per station
  • Have exhaust inlets no more than 12 inches from the point of chemical application

This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.

Why Proper Ventilation Matters

Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.

Exhaust Flow and Placement

IMC Section 403.3 defines how source capture ventilation must operate:

  • Exhaust rate: at least 50 CFM per station
  • Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
  • Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)

When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.

Code-Compliant Solution

The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.

 

Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.

South Carolina

IMC Code Requirements for Nail Salons in SOUTH CAROLINA

What the IMC Code Requires

For new nail salons in the state of South Carolina, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:

  • Exhaust a minimum of 50 CFM (cubic feet per minute) per station
  • Have exhaust inlets no more than 12 inches from the point of chemical application

This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.

Why Proper Ventilation Matters

Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.

Exhaust Flow and Placement

IMC Section 403.3 defines how source capture ventilation must operate:

  • Exhaust rate: at least 50 CFM per station
  • Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
  • Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)

When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.

Code-Compliant Solution

The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.

 

Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.

Tennessee

IMC Code Requirements for Nail Salons in TENNESSEE

What the IMC Code Requires

For new nail salons in the state of Tennessee, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:

  • Exhaust a minimum of 50 CFM (cubic feet per minute) per station
  • Have exhaust inlets no more than 12 inches from the point of chemical application

This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.

Why Proper Ventilation Matters

Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.

Exhaust Flow and Placement

IMC Section 403.3 defines how source capture ventilation must operate:

  • Exhaust rate: at least 50 CFM per station
  • Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
  • Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)

When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.

Code-Compliant Solution

The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.

 

Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.

Texas

IMC Code Requirements for Nail Salons in TEXAS

What the IMC Code Requires

For new nail salons in the state of Texas, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station.
Each system must:

  • Exhaust a minimum of 50 CFM (cubic feet per minute) per station
  • Have exhaust inlets no more than 12 inches from the point of chemical application

This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.

Why Proper Ventilation Matters

Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.

Exhaust Flow and Placement

IMC Section 403.3 defines how source capture ventilation must operate:

  • Exhaust rate: at least 50 CFM per station
  • Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
  • Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)

When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.

Code-Compliant Solution

The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.

 

Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.

Utah

IMC Code Requirements for Nail Salons in UTAH

What the IMC Code Requires

For new nail salons in the state of Utah, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station.
Each system must:

  • Exhaust a minimum of 50 CFM (cubic feet per minute) per station
  • Have exhaust inlets no more than 12 inches from the point of chemical application

This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.

Why Proper Ventilation Matters

Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.

Exhaust Flow and Placement

IMC Section 403.3 defines how source capture ventilation must operate:

  • Exhaust rate: at least 50 CFM per station
  • Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
  • Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)

When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.

Code-Compliant Solution

The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.

 

Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.

Virginia

IMC Code Requirements for Nail Salons in VIRGINIA

What the IMC Code Requires

For new nail salons in the state of Virginia, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station.  Each system must:

  • Exhaust a minimum of 50 CFM (cubic feet per minute) per station
  • Have exhaust inlets no more than 12 inches from the point of chemical application

This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.

Why Proper Ventilation Matters

Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.

Exhaust Flow and Placement

IMC Section 403.3 defines how source capture ventilation must operate:

  • Exhaust rate: at least 50 CFM per station
  • Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
  • Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)

When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.

Code-Compliant Solution

The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.

 

Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.

Washington

IMC Code Requirements for Nail Salons in WASHINGTON

What the IMC Code Requires

For new nail salons in the state of Washington, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:

  • Exhaust a minimum of 50 CFM (cubic feet per minute) per station
  • Have exhaust inlets no more than 12 inches from the point of chemical application

This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.

Why Proper Ventilation Matters

Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.

Exhaust Flow and Placement

IMC Section 403.3 defines how source capture ventilation must operate:

  • Exhaust rate: at least 50 CFM per station
  • Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
  • Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)

When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.

Code-Compliant Solution

The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.

 

Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.

Wisconsin

IMC Code Requirements for Nail Salons in WISCONSIN

What the IMC Code Requires

For new nail salons in the state of Wisconsin, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station.  Each system must:

  • Exhaust a minimum of 50 CFM (cubic feet per minute) per station
  • Have exhaust inlets no more than 12 inches from the point of chemical application

This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.

Why Proper Ventilation Matters

Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.

Exhaust Flow and Placement

IMC Section 403.3 defines how source capture ventilation must operate:

  • Exhaust rate: at least 50 CFM per station
  • Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
  • Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)

When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.

Code-Compliant Solution

The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.

 

Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.

Wyoming

Code Requirements for Nail Salons in WYOMING

What the IMC Code Requires

For new nail salons in the state of Wyoming, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station.  Each system must:

  • Exhaust a minimum of 50 CFM (cubic feet per minute) per station
  • Have exhaust inlets no more than 12 inches from the point of chemical application

This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.

Why Proper Ventilation Matters

Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.

Exhaust Flow and Placement

IMC Section 403.3 defines how source capture ventilation must operate:

  • Exhaust rate: at least 50 CFM per station
  • Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
  • Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)

When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.

Code-Compliant Solution

The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.

 

Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.

Read Our Reviews

Trusted by Salons & Spas

“I truly believe that this system has helped improve my health and will make it possible to continue to work in this industry for longer. I am in the process of opening another salon and I am installing air filters in both new tables. I can't recommend enough how important this filter is and how it helped me. I strongly recommend it to all nail technicians, whether you are in the beginning of your career or a veteran filer."

Debbie Wensman

OPI School Account Consultant, Acrylics Down Under

“I recently purchased 3 Salon Pure Air units and I must say that I love, love, love them! I was concerned about not only my health and the health of my clients, but my children are in the salon on a regular basis, and I wanted to be sure they were not breathing in harmful fumes. We set up the units and we are now odor free and worry free. Thank you, Salon Pure Air, for your exceptional product. It was well worth the investment!”

Tam Nguyen

Owner, Model Nails

“When I started using my Salon Pure Air my business increased for my hair department. All of our guests love the fact that we do nails without all that odor. I'll never do nails again without this air system. It's Awesome!"

Christine Brunner

Creative Grand Master Nail Tech, Wild Horse Salon

Shop Air Purifiers

From nail salons and hair salons to medi-spas and tattoo studios, Salon Pure Air® systems deliver powerful, compact, and efficient solutions tailored to your environment.