Regulatory Information
Please select your state below to learn more about your state’s regulatory information.
Alabama
Code Requirements for Nail Salons in ALABAMA
What the IMC Code Requires
For new nail salons in the state of Alabama, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:
- Exhaust a minimum of 50 CFM (cubic feet per minute) per station
- Have exhaust inlets no more than 12 inches from the point of chemical application
This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.
Why Proper Ventilation Matters
Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.
Exhaust Flow and Placement
IMC Section 403.3 defines how source capture ventilation must operate:
- Exhaust rate: at least 50 CFM per station
- Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
- Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)
When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.
Code-Compliant Solution
The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.
Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.
Alaska
Code Requirements for Nail Salons in ALASKA
What the IMC Code Requires
For new nail salons in the state of Alaska, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:
- Exhaust a minimum of 50 CFM (cubic feet per minute) per station
- Have exhaust inlets no more than 12 inches from the point of chemical application
This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.
Why Proper Ventilation Matters
Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.
Exhaust Flow and Placement
IMC Section 403.3 defines how source capture ventilation must operate:
- Exhaust rate: at least 50 CFM per station
- Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
- Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)
When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.
Code-Compliant Solution
The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.
Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.
Arizona
IMC Code Requirements for Nail Salons in ARIZONA
What the IMC Code Requires
For new nail salons in the state of Arizona, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:
- Exhaust a minimum of 50 CFM (cubic feet per minute) per station
- Have exhaust inlets no more than 12 inches from the point of chemical application
This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.
Why Proper Ventilation Matters
Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.
Exhaust Flow and Placement
IMC Section 403.3 defines how source capture ventilation must operate:
- Exhaust rate: at least 50 CFM per station
- Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
- Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)
When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.
Code-Compliant Solution
The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.
Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.
Arkansas
Code Requirements for Nail Salons in ARKANSAS
What the IMC Code Requires
For new nail salons in the state of Arkansas, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:
- Exhaust a minimum of 50 CFM (cubic feet per minute) per station
- Have exhaust inlets no more than 12 inches from the point of chemical application
This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.
Why Proper Ventilation Matters
Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.
Exhaust Flow and Placement
IMC Section 403.3 defines how source capture ventilation must operate:
- Exhaust rate: at least 50 CFM per station
- Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
- Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)
When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.
Code-Compliant Solution
The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.
Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.
Colorado
IMC Code Requirements for Nail Salons in COLORADO
What the IMC Code Requires
For new nail salons in the state of Colorado, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:
- Exhaust a minimum of 50 CFM (cubic feet per minute) per station
- Have exhaust inlets no more than 12 inches from the point of chemical application
This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.
Why Proper Ventilation Matters
Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.
Exhaust Flow and Placement
IMC Section 403.3 defines how source capture ventilation must operate:
- Exhaust rate: at least 50 CFM per station
- Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
- Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)
When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.
Code-Compliant Solution
The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.
Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.
Connecticut
IMC Code Requirements for Nail Salons in CONNECTICUT
What the IMC Code Requires
For new nail salons in the state of Connecticut, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:
- Exhaust a minimum of 50 CFM (cubic feet per minute) per station
- Have exhaust inlets no more than 12 inches from the point of chemical application
This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.
Why Proper Ventilation Matters
Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.
Exhaust Flow and Placement
IMC Section 403.3 defines how source capture ventilation must operate:
- Exhaust rate: at least 50 CFM per station
- Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
- Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)
When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.
Code-Compliant Solution
The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.
Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.
Florida
IMC Code Requirements for Nail Salons in FLORIDA
What the IMC Code Requires
For new nail salons in the state of Florida, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station.
Each system must:
- Exhaust a minimum of 50 CFM (cubic feet per minute) per station
- Have exhaust inlets no more than 12 inches from the point of chemical application
This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.
Why Proper Ventilation Matters
Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.
Exhaust Flow and Placement
IMC Section 403.3 defines how source capture ventilation must operate:
- Exhaust rate: at least 50 CFM per station
- Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
- Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)
When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.
Code-Compliant Solution
The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.
Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.
Georgia
IMC Code Requirements for Nail Salons in GEORGIA
What the IMC Code Requires
For new nail salons in the state of Georgia, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:
- Exhaust a minimum of 50 CFM (cubic feet per minute) per station
- Have exhaust inlets no more than 12 inches from the point of chemical application
This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.
Why Proper Ventilation Matters
Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.
Exhaust Flow and Placement
IMC Section 403.3 defines how source capture ventilation must operate:
- Exhaust rate: at least 50 CFM per station
- Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
- Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)
When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.
Code-Compliant Solution
The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.
Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.
Illinois
IMC Code Requirements for Nail Salons in ILLINOIS
What the IMC Code Requires
For new nail salons in the state of Illinois, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station.
Each system must:
- Exhaust a minimum of 50 CFM (cubic feet per minute) per station
- Have exhaust inlets no more than 12 inches from the point of chemical application
This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.
Why Proper Ventilation Matters
Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.
Exhaust Flow and Placement
IMC Section 403.3 defines how source capture ventilation must operate:
- Exhaust rate: at least 50 CFM per station
- Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
- Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)
When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.
Code-Compliant Solution
The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.
Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.
Indiana
IMC Code Requirements for Nail Salons in INDIANA
What the IMC Code Requires
For new nail salons in the state of Indiana, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:
- Exhaust a minimum of 50 CFM (cubic feet per minute) per station
- Have exhaust inlets no more than 12 inches from the point of chemical application
This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.
Why Proper Ventilation Matters
Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.
Exhaust Flow and Placement
IMC Section 403.3 defines how source capture ventilation must operate:
- Exhaust rate: at least 50 CFM per station
- Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
- Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)
When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.
Code-Compliant Solution
The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.
Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.
Iowa
Code Requirements for Nail Salons in IOWA
What the IMC Code Requires
For new nail salons in the state of Iowa, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:
- Exhaust a minimum of 50 CFM (cubic feet per minute) per station
- Have exhaust inlets no more than 12 inches from the point of chemical application
This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.
Why Proper Ventilation Matters
Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.
Exhaust Flow and Placement
IMC Section 403.3 defines how source capture ventilation must operate:
- Exhaust rate: at least 50 CFM per station
- Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
- Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)
When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.
Code-Compliant Solution
The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.
Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.
Louisiana
IMC Code Requirements for Nail Salons in LOUISIANA
What the IMC Code Requires
For new nail salons in the state of Louisiana, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:
- Exhaust a minimum of 50 CFM (cubic feet per minute) per station
- Have exhaust inlets no more than 12 inches from the point of chemical application
This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.
Why Proper Ventilation Matters
Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.
Exhaust Flow and Placement
IMC Section 403.3 defines how source capture ventilation must operate:
- Exhaust rate: at least 50 CFM per station
- Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
- Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)
When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.
Code-Compliant Solution
The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.
Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.
Maine
Code Requirements for Nail Salons in MAINE
What the IMC Code Requires
For new nail salons in the state of Maine, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:
- Exhaust a minimum of 50 CFM (cubic feet per minute) per station
- Have exhaust inlets no more than 12 inches from the point of chemical application
This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.
Why Proper Ventilation Matters
Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.
Exhaust Flow and Placement
IMC Section 403.3 defines how source capture ventilation must operate:
- Exhaust rate: at least 50 CFM per station
- Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
- Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)
When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.
Code-Compliant Solution
The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.
Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.
Maryland
IMC Code Requirements for Nail Salons in MARYLAND
What the IMC Code Requires
For new nail salons in the state of Maryland, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:
- Exhaust a minimum of 50 CFM (cubic feet per minute) per station
- Have exhaust inlets no more than 12 inches from the point of chemical application
This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.
Why Proper Ventilation Matters
Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.
Exhaust Flow and Placement
IMC Section 403.3 defines how source capture ventilation must operate:
- Exhaust rate: at least 50 CFM per station
- Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
- Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)
When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.
Code-Compliant Solution
The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.
Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.
Massachusetts
IMC Code Requirements for Nail Salons in MASSACHUSETTS
What the IMC Code Requires
For new nail salons in the state of Massachusetts, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:
- Exhaust a minimum of 50 CFM (cubic feet per minute) per station
- Have exhaust inlets no more than 12 inches from the point of chemical application
This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.
Why Proper Ventilation Matters
Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.
Exhaust Flow and Placement
IMC Section 403.3 defines how source capture ventilation must operate:
- Exhaust rate: at least 50 CFM per station
- Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
- Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)
When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.
Code-Compliant Solution
The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.
Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.
Michigan
IMC Code Requirements for Nail Salons in MICHIGAN
What the IMC Code Requires
For new nail salons in the state of Michigan, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:
- Exhaust a minimum of 50 CFM (cubic feet per minute) per station
- Have exhaust inlets no more than 12 inches from the point of chemical application
This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.
Why Proper Ventilation Matters
Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.
Exhaust Flow and Placement
IMC Section 403.3 defines how source capture ventilation must operate:
- Exhaust rate: at least 50 CFM per station
- Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
- Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)
When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.
Code-Compliant Solution
The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.
Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.
Minnesota
IMC Code Requirements for Nail Salons in MINNESOTA
What the IMC Code Requires
For new nail salons in the state of Minnesota, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:
- Exhaust a minimum of 50 CFM (cubic feet per minute) per station
- Have exhaust inlets no more than 12 inches from the point of chemical application
This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.
Why Proper Ventilation Matters
Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.
Exhaust Flow and Placement
IMC Section 403.3 defines how source capture ventilation must operate:
- Exhaust rate: at least 50 CFM per station
- Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
- Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)
When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.
Code-Compliant Solution
The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.
Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.
Missouri
IMC Code Requirements for Nail Salons in MISSOURI
What the IMC Code Requires
For new nail salons in the state of Missouri, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:
- Exhaust a minimum of 50 CFM (cubic feet per minute) per station
- Have exhaust inlets no more than 12 inches from the point of chemical application
This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.
Why Proper Ventilation Matters
Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.
Exhaust Flow and Placement
IMC Section 403.3 defines how source capture ventilation must operate:
- Exhaust rate: at least 50 CFM per station
- Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
- Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)
When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.
Code-Compliant Solution
The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.
Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.
Montana
Code Requirements for Nail Salons in MONTANA
What the IMC Code Requires
For new nail salons in the state of Montana, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:
- Exhaust a minimum of 50 CFM (cubic feet per minute) per station
- Have exhaust inlets no more than 12 inches from the point of chemical application
This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.
Why Proper Ventilation Matters
Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.
Exhaust Flow and Placement
IMC Section 403.3 defines how source capture ventilation must operate:
- Exhaust rate: at least 50 CFM per station
- Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
- Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)
When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.
Code-Compliant Solution
The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.
Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.
Nevada
IMC Code Requirements for Nail Salons in NEVADA
What the IMC Code Requires
For new nail salons in the state of Nevada, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:
- Exhaust a minimum of 50 CFM (cubic feet per minute) per station
- Have exhaust inlets no more than 12 inches from the point of chemical application
This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.
Why Proper Ventilation Matters
Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.
Exhaust Flow and Placement
IMC Section 403.3 defines how source capture ventilation must operate:
- Exhaust rate: at least 50 CFM per station
- Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
- Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)
When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.
Code-Compliant Solution
The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.
Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.
New Hampshire
Code Requirements for Nail Salons in NEW HAMPSHIRE
What the IMC Code Requires
For new nail salons in the state of New Hampshire, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:
- Exhaust a minimum of 50 CFM (cubic feet per minute) per station
- Have exhaust inlets no more than 12 inches from the point of chemical application
This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.
Why Proper Ventilation Matters
Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.
Exhaust Flow and Placement
IMC Section 403.3 defines how source capture ventilation must operate:
- Exhaust rate: at least 50 CFM per station
- Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
- Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)
When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.
Code-Compliant Solution
The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.
Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.
New Jersey
IMC Code Requirements for Nail Salons in NEW JERSEY
What the IMC Code Requires
For new nail salons in the state of New Jersey, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:
- Exhaust a minimum of 50 CFM (cubic feet per minute) per station
- Have exhaust inlets no more than 12 inches from the point of chemical application
This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.
Why Proper Ventilation Matters
Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.
Exhaust Flow and Placement
IMC Section 403.3 defines how source capture ventilation must operate:
- Exhaust rate: at least 50 CFM per station
- Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
- Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)
When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.
Code-Compliant Solution
The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.
Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.
New York
IMC Code Requirements for Nail Salons in NEW YORK
What the IMC Code Requires
For new nail salons in the state of New York, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:
- Exhaust a minimum of 50 CFM (cubic feet per minute) per station
- Have exhaust inlets no more than 12 inches from the point of chemical application
This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.
Why Proper Ventilation Matters
Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.
Exhaust Flow and Placement
IMC Section 403.3 defines how source capture ventilation must operate:
- Exhaust rate: at least 50 CFM per station
- Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
- Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)
When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.
Code-Compliant Solution
The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.
Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.
North Carolina
IMC Code Requirements for Nail Salons in NORTH CAROLINA
What the IMC Code Requires
For new nail salons in the state of North Carolina, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:
- Exhaust a minimum of 50 CFM (cubic feet per minute) per station
- Have exhaust inlets no more than 12 inches from the point of chemical application
This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.
Why Proper Ventilation Matters
Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.
Exhaust Flow and Placement
IMC Section 403.3 defines how source capture ventilation must operate:
- Exhaust rate: at least 50 CFM per station
- Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
- Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)
When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.
Code-Compliant Solution
The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.
Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.
North Dakota
Code Requirements for Nail Salons in NORTH DAKOTA
What the IMC Code Requires
For new nail salons in the state of North Dakota, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:
- Exhaust a minimum of 50 CFM (cubic feet per minute) per station
- Have exhaust inlets no more than 12 inches from the point of chemical application
This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.
Why Proper Ventilation Matters
Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.
Exhaust Flow and Placement
IMC Section 403.3 defines how source capture ventilation must operate:
- Exhaust rate: at least 50 CFM per station
- Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
- Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)
When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.
Code-Compliant Solution
The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.
Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.
Ohio
IMC Code Requirements for Nail Salons in OHIO
What the IMC Code Requires
For new nail salons in the state of Ohio, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station.
Each system must:
- Exhaust a minimum of 50 CFM (cubic feet per minute) per station
- Have exhaust inlets no more than 12 inches from the point of chemical application
This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.
Why Proper Ventilation Matters
Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.
Exhaust Flow and Placement
IMC Section 403.3 defines how source capture ventilation must operate:
- Exhaust rate: at least 50 CFM per station
- Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
- Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)
When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.
Code-Compliant Solution
The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.
Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.
Oregon
IMC Code Requirements for Nail Salons in OREGON
What the IMC Code Requires
For new nail salons in the state of Oregon, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:
- Exhaust a minimum of 50 CFM (cubic feet per minute) per station
- Have exhaust inlets no more than 12 inches from the point of chemical application
This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.
Why Proper Ventilation Matters
Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.
Exhaust Flow and Placement
IMC Section 403.3 defines how source capture ventilation must operate:
- Exhaust rate: at least 50 CFM per station
- Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
- Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)
When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.
Code-Compliant Solution
The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.
Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.
Pennsylvania
IMC Code Requirements for Nail Salons in PENNSYLVANIA
What the IMC Code Requires
For new nail salons in the state of Pennsylvania, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:
- Exhaust a minimum of 50 CFM (cubic feet per minute) per station
- Have exhaust inlets no more than 12 inches from the point of chemical application
This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.
Why Proper Ventilation Matters
Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.
Exhaust Flow and Placement
IMC Section 403.3 defines how source capture ventilation must operate:
- Exhaust rate: at least 50 CFM per station
- Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
- Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)
When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.
Code-Compliant Solution
The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.
Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.
South Carolina
IMC Code Requirements for Nail Salons in SOUTH CAROLINA
What the IMC Code Requires
For new nail salons in the state of South Carolina, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:
- Exhaust a minimum of 50 CFM (cubic feet per minute) per station
- Have exhaust inlets no more than 12 inches from the point of chemical application
This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.
Why Proper Ventilation Matters
Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.
Exhaust Flow and Placement
IMC Section 403.3 defines how source capture ventilation must operate:
- Exhaust rate: at least 50 CFM per station
- Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
- Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)
When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.
Code-Compliant Solution
The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.
Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.
Tennessee
IMC Code Requirements for Nail Salons in TENNESSEE
What the IMC Code Requires
For new nail salons in the state of Tennessee, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:
- Exhaust a minimum of 50 CFM (cubic feet per minute) per station
- Have exhaust inlets no more than 12 inches from the point of chemical application
This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.
Why Proper Ventilation Matters
Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.
Exhaust Flow and Placement
IMC Section 403.3 defines how source capture ventilation must operate:
- Exhaust rate: at least 50 CFM per station
- Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
- Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)
When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.
Code-Compliant Solution
The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.
Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.
Texas
IMC Code Requirements for Nail Salons in TEXAS
What the IMC Code Requires
For new nail salons in the state of Texas, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station.
Each system must:
- Exhaust a minimum of 50 CFM (cubic feet per minute) per station
- Have exhaust inlets no more than 12 inches from the point of chemical application
This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.
Why Proper Ventilation Matters
Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.
Exhaust Flow and Placement
IMC Section 403.3 defines how source capture ventilation must operate:
- Exhaust rate: at least 50 CFM per station
- Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
- Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)
When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.
Code-Compliant Solution
The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.
Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.
Utah
IMC Code Requirements for Nail Salons in UTAH
What the IMC Code Requires
For new nail salons in the state of Utah, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station.
Each system must:
- Exhaust a minimum of 50 CFM (cubic feet per minute) per station
- Have exhaust inlets no more than 12 inches from the point of chemical application
This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.
Why Proper Ventilation Matters
Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.
Exhaust Flow and Placement
IMC Section 403.3 defines how source capture ventilation must operate:
- Exhaust rate: at least 50 CFM per station
- Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
- Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)
When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.
Code-Compliant Solution
The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.
Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.
Virginia
IMC Code Requirements for Nail Salons in VIRGINIA
What the IMC Code Requires
For new nail salons in the state of Virginia, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:
- Exhaust a minimum of 50 CFM (cubic feet per minute) per station
- Have exhaust inlets no more than 12 inches from the point of chemical application
This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.
Why Proper Ventilation Matters
Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.
Exhaust Flow and Placement
IMC Section 403.3 defines how source capture ventilation must operate:
- Exhaust rate: at least 50 CFM per station
- Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
- Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)
When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.
Code-Compliant Solution
The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.
Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.
Washington
IMC Code Requirements for Nail Salons in WASHINGTON
What the IMC Code Requires
For new nail salons in the state of Washington, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:
- Exhaust a minimum of 50 CFM (cubic feet per minute) per station
- Have exhaust inlets no more than 12 inches from the point of chemical application
This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.
Why Proper Ventilation Matters
Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.
Exhaust Flow and Placement
IMC Section 403.3 defines how source capture ventilation must operate:
- Exhaust rate: at least 50 CFM per station
- Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
- Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)
When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.
Code-Compliant Solution
The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.
Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.
Wisconsin
IMC Code Requirements for Nail Salons in WISCONSIN
What the IMC Code Requires
For new nail salons in the state of Wisconsin, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:
- Exhaust a minimum of 50 CFM (cubic feet per minute) per station
- Have exhaust inlets no more than 12 inches from the point of chemical application
This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.
Why Proper Ventilation Matters
Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.
Exhaust Flow and Placement
IMC Section 403.3 defines how source capture ventilation must operate:
- Exhaust rate: at least 50 CFM per station
- Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
- Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)
When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.
Code-Compliant Solution
The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.
Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.
Wyoming
Code Requirements for Nail Salons in WYOMING
What the IMC Code Requires
For new nail salons in the state of Wyoming, the International Mechanical Code (IMC) requires a source capture ventilation system at every manicure and pedicure station. Each system must:
- Exhaust a minimum of 50 CFM (cubic feet per minute) per station
- Have exhaust inlets no more than 12 inches from the point of chemical application
This ensures that harmful vapors and dust are removed directly at the source—before they enter the breathing zone.
Why Proper Ventilation Matters
Nail products often contain chemicals like acetone, isopropyl alcohol, and formaldehyde, which can release harmful fumes and ultra-fine particles. Without effective ventilation, these contaminants can lead to irritation, headaches, and long-term health risks.
Source capture ventilation protects both technicians and clients, helping salons maintain a cleaner, safer, and more compliant environment.
Exhaust Flow and Placement
IMC Section 403.3 defines how source capture ventilation must operate:
- Exhaust rate: at least 50 CFM per station
- Inlet placement: within 12 inches of the chemical source (horizontal or vertical)
- Outdoor exhaust outlet: at least 10 ft from property lines and openings, 3 ft from walls or roofs, and 10 ft above ground (IMC Section 501.3.1)
When source capture systems run continuously during salon hours, the airflow can count toward overall ventilation rates required in IMC Table 403.3.1.1.
Code-Compliant Solution
The Salon Pure Air®3 meets all IMC ventilation code requirements for nail salons—providing powerful source capture performance in the smallest and quietest code-compliant system available.
Please note: The information provided here is accurate as of the date of publication. Because regulations and requirements can change, always confirm the most up-to-date codes with your local or state authorities before making compliance decisions.
Read Our Reviews
Trusted by Salons & Spas
“I truly believe that this system has helped improve my health and will make it possible to continue to work in this industry for longer. I am in the process of opening another salon and I am installing air filters in both new tables. I can't recommend enough how important this filter is and how it helped me. I strongly recommend it to all nail technicians, whether you are in the beginning of your career or a veteran filer."
“I recently purchased 3 Salon Pure Air units and I must say that I love, love, love them! I was concerned about not only my health and the health of my clients, but my children are in the salon on a regular basis, and I wanted to be sure they were not breathing in harmful fumes. We set up the units and we are now odor free and worry free. Thank you, Salon Pure Air, for your exceptional product. It was well worth the investment!”
“When I started using my Salon Pure Air my business increased for my hair department. All of our guests love the fact that we do nails without all that odor. I'll never do nails again without this air system. It's Awesome!"
Shop Air Purifiers
From nail salons and hair salons to medi-spas and tattoo studios, Salon Pure Air® systems deliver powerful, compact, and efficient solutions tailored to your environment.